Application Guidelines

Aveng Infraset concrete poles and masts are manufactured in ISO 9001-2008 accredited factories in Gauteng, KwaZulu-Natal and the Northern Cape. They are available in a wide range of strengths and sizes designed to fill most MV and LV line requirements, and comply with Eskom DTC 0106 and various SABS and Transnet specifi cations.

Application and installation guidelines must be followed to ensure that poles and applications are properly matched.

Design criteria for LV lines

Table 1: Arial bundled conductors

LV Lines:
Aerial bundled conductors
Wind span (m)
7m 4kN Concrete 9m 4kN Concrete 7.2m 10kN Concrete 7.5m 20kN Concrete
Type of ABC
35mm square single 60 54 130 240
35mm square double 30 26 75 120
70mm sqaure single 48 44 110 220
70mm square double 24 22 55 120

Design criteria for MV lines

Table 2: Fox conductor - shielded

MV Lines:
Typical 22kV Fox
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 9m 4kN Concrete 80 80 80 80 80 80
9m 7kN Concrete 170 170 170 170 170 170
9.3m 17.5kN Concrete 490 490 490 490 490 490
10m 6kN Concrete 135 135 135 135 135 135
10m 8kN Concrete 195 195 195 195 195 195
10m 12.4kN Concrete 320 320 320 320 320 320
10m 16.8kN Concrete 450 450 450 450 450 450
11m 6kN Concrete 130 130 130 130 130 130
11m 8kN Concrete 190 190 190 190 190 190
11m 10.9kN Concrete 260 260 260 260 260 260
11m 14.9kN Concrete 380 380 380 380 380 380
Number of bisector stays     1 2 2  
Number of inline stays   2       2

Table 3: Fox conductor - unshielded

MV Lines:
Typical 22kV Fox
Conductor – Unshielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 9m 4kN Concrete 110 110 110 110 110 110
9m 7kN Concrete 235 235 235 235 235 235
9.3m 17.5kN Concrete 600 600 600 600 600 600
10m 6kN Concrete 185 185 185 185 185 185
10m 8kN Concrete 265 265 265 265 265 265
10m 12.4kN Concrete 430 430 430 430 430 430
10m 16.8kN Concrete 620 620 620 620 620 620
11m 6kN Concrete 175 175 175 175 175 175
11m 8kN Concrete 255 255 255 255 255 255
11m 10.9kN Concrete 370 370 370 370 370 370
11m 14.9kN Concrete 530 530 530 530 530 530
Number of bisector stays     1 2 2  
Number of inline stays   2       2

Table 4: Mink conductor - shielded

MV Lines:
Typical 22kV Mink
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 640          
Wind span (m) 9m 4kN Concrete 65 65 65 65 65 65
9m 7kN Concrete 140 140 140 140 140 140
9.3m 17.5kN Concrete 400 400 400 400 400 400
10m 6kN Concrete 110 110 110 110 110 110
10m 8kN Concrete 160 160 160 160 160 160
10m 12.4kN Concrete 260 260 260 260 260 260
10m 16.8kN Concrete 370 370 370 370 370 370
11m 6kN Concrete 105 105 105 105 105 105
11m 8kN Concrete 155 155 155 155 155 155
11m 10.9kN Concrete 210 210 210 210 210 210
11m 14.9kN Concrete 310 310 310 310 310 310
Number of bisector stays     1 2 3  
Number of inline stays   2       2

Table 5: Mink conductor - unshielded

MV Lines:
Typical 22kV Mink
Conductor – Unshielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 640          
Wind span (m) 9m 4kN Concrete 80 80 80 80 80 80
9m 7kN Concrete 175 175 175 175 175 175
9.3m 17.5kN Concrete 500 500 500 500 500 500
10m 6kN Concrete 140 140 140 140 140 140
10m 8kN Concrete 205 205 205 205 205 205
10m 12.4kN Concrete 330 330 330 330 330 330
10m 16.8kN Concrete 460 460 460 460 460 460
11m 6kN Concrete 130 130 130 130 130 130
11m 8kN Concrete 195 195 195 195 195 195
11m 10.9kN Concrete 280 280 280 280 280 280
11m 14.9kN Concrete 400 400 400 400 400 400
Number of bisector stays     1 2 2  
Number of inline stays   2       2

Table 6: Hare conductor - shielded

MV Lines:
Typical 22kV Hare
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 380          
Wind span (m) 9m 4kN Concrete 55 55 55 55 55 55
9m 7kN Concrete 115 115 115 115 115 115
9.3m 17.5kN Concrete 320 320 320 320 320 320
10m 6kN Concrete 90 90 90 90 90 90
10m 8kN Concrete 135 135 135 135 135 135
10m 12.4kN Concrete 210 210 210 210 210 210
10m 16.8kN Concrete 300 300 300 300 300 300
11m 6kN Concrete 85 85 85 85 85 85
11m 8kN Concrete 125 125 125 125 125 125
11m 10.9kN Concrete 170 170 170 170 170 170
11m 14.9kN Concrete 250 250 250 250 250 250
Number of bisector stays     1 2 3  
Number of inline stays   2       3

Table 7: Hare conductor - unshielded

MV Lines:
Typical 22kV Fox
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 380          
Wind span (m) 9m 4kN Concrete 65 65 65 65 65 65
9m 7kN Concrete 135 135 135 135 135 135
9.3m 17.5kN Concrete 380 380 380 380 380 380
10m 6kN Concrete 110 110 110 110 110 110
10m 8kN Concrete 155 155 155 155 155 155
10m 12.4kN Concrete 250 250 250 250 250 250
10m 16.8kN Concrete 360 360 360 360 360 360
11m 6kN Concrete 100 100 100 100 100 100
11m 8kN Concrete 150 150 150 150 150 150
11m 10.9kN Concrete 200 200 200 200 200 200
11m 14.9kN Concrete 300 300 300 300 300 300
Number of bisector stays     1 2 3  
Number of inline stays   2       3

Design criteria for heavy conductor lines

Table 8: Bear conductor - shielded

Heavy Lines:
Typical 33kV Bear
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 185 100 100 100 100 100
Weight span (m) 336          
Wind span (m) 12m 9.8kN Concrete 105 105 105 105 105 105
12m 13.3kN Concrete 150 150 150 150 150 150
12m 17.7kN Concrete 210 210 210 210 210 210
13m 10kN Concrete 92 92 92 92 92 92
13m 12.1kN Concrete 130 130 130 130 130 130
13m 16.0kN Concrete 185 185 185 185 185 185
14m 11.0kN Concrete 115 115 115 115 115 115
14m 14.7kN Concrete 160 160 160 160 160 160
Number of bisector stays     2 4 5  
Number of inline stays   4       5

Table 9: Bear conductor - unshielded

Heavy Lines:
Typical 33kV Bear
Conductor – Unshielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 185 100 100 100 100 100
Weight span (m) 336          
Wind span (m) 12m 9.8kN Concrete 115 115 115 115 115 115
12m 13.3kN Concrete 165 165 165 165 165 165
12m 17.7kN Concrete 230 230 230 230 230 230
13m 10kN Concrete 100 100 100 100 100 100
13m 12.1kN Concrete 145 145 145 145 145 145
13m 16.0kN Concrete 200 200 200 200 200 200
14m 11.0kN Concrete 125 125 125 125 125 125
14m 14.7kN Concrete 180 180 180 180 180 180
Number of bisector stays     2 4 6  
Number of inline stays   3       4

Table 10: Wolf conductor - shielded

Heavy Lines:
Typical 33kV Wolf
Conductor – Shielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 185 100 100 100 100 100
Weight span (m) 561          
Wind span (m) 12m 9.8kN Concrete 130 130 130 130 130 130
12m 13.3kN Concrete 190 190 190 190 190 190
12m 17.7kN Concrete 260 260 260 260 260 260
13m 10kN Concrete 100 100 100 100 100 100
13m 12.1kN Concrete 165 165 165 165 165 165
13m 16.0kN Concrete 230 230 230 230 230 230
14m 11.0kN Concrete 135 135 135 135 135 135
14m 14.7kN Concrete 190 190 190 190 190 190
Number of bisector stays     2 3 4  
Number of inline stays   3       4

Table 11: Wolf conductor - unshielded

Heavy Lines:
Typical 33kV Wolf
Conductor – Unshielded
Pole application Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 185 100 100 100 100 100
Weight span (m) 561          
Wind span (m) 12m 9.8kN Concrete 145 145 145 145 145 145
12m 13.3kN Concrete 215 215 215 215 215 215
12m 17.7kN Concrete 295 295 295 295 295 295
13m 10kN Concrete 125 125 125 125 125 125
13m 12.1kN Concrete 185 185 185 185 185 185
13m 16.0kN Concrete 260 260 260 260 260 260
14m 11.0kN Concrete 165 165 165 165 165 165
14m 14.7kN Concrete 230 230 230 230 230 230
Number of bisector stays     2 3 4  
Number of inline stays   3       3

Design criteria for double-circuit lines

Table 12: MV Mink D Circuit - unshielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1090          
Wind span (m) 11m 10.9kN Concrete 123 245 221 196 172 196
11m 13.3kN Concrete 180 361 325 289 253 289
12m 17.4kN Concrete 154 309 278 247 216 247
12m 10kN Concrete 218 436 392 349 305 349
13m 12.1kN Concrete 134 268 241 241 188 214
13m 16.0kN Concrete 190 381 343 305 266 305
14m 11.0kN Concrete 115 229 206 183 160 183
14m 14.7kN Concrete 168 336 303 269 235 269
Number of bisector stays     1 2 2  
Number of inline stays   1       2

Table 13: MV Mink D Circuit - shielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 106 187 168 150 131 150
11m 13.3kN Concrete 156 275 248 220 193 220
12m 17.4kN Concrete 134 236 212 188 165 188
12m 10kN Concrete 189 333 299 266 233 266
13m 12.1kN Concrete 116 204 184 164 143 164
13m 16.0kN Concrete 165 290 261 232 203 232
14m 11.0kN Concrete 99 175 157 140 122 140
14m 14.7kN Concrete 146 257 231 205 180 205
Number of bisector stays     1 2 2  
Number of inline stays   1       2

Table 14: MV Mink Hare - unshielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 95 190 171 152 133 152
11m 13.3kN Concrete 140 280 252 224 196 224
12m 17.4kN Concrete 120 239 215 191 168 191
12m 10kN Concrete 169 338 304 270 237 270
13m 12.1kN Concrete 104 208 187 166 145 166
13m 16.0kN Concrete 148 295 266 236 207 236
14m 11.0kN Concrete 89 178 160 142 124 142
14m 14.7kN Concrete 130 261 235 209 182 209
Number of bisector stays     2 3 3  
Number of inline stays   1       3

Design criteria for double-circuit lines

Table 15: MV Mink Hare - shielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 95 190 171 152 133 152
11m 13.3kN Concrete 140 280 252 224 196 224
12m 17.4kN Concrete 120 239 215 191 168 191
12m 10kN Concrete 169 338 304 270 237 270
13m 12.1kN Concrete 104 208 187 166 145 166
13m 16.0kN Concrete 148 295 266 236 207 236
14m 11.0kN Concrete 89 178 160 142 124 142
14m 14.7kN Concrete 130 261 235 209 182 209
Number of bisector stays     2 3 3  
Number of inline stays   1       3

Table 16: MV Wolf - unshielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 74 149 134 119 104 119
11m 13.3kN Concrete 109 219 197 175 153 175
12m 17.4kN Concrete 93 187 168 150 131 150
12m 10kN Concrete 132 264 238 211 185 211
13m 12.1kN Concrete 81 162 146 130 114 130
13m 16.0kN Concrete 115 231 207 184 161 184
14m 11.0kN Concrete 69 139 125 111 97 111
14m 14.7kN Concrete 102 204 183 163 143 163
Number of bisector stays     2 3 3  
Number of inline stays   2       3

Table 17: MV Wolf - shielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 68 125 113 100 88 100
11m 13.3kN Concrete 100 184 166 147 129 147
12m 17.4kN Concrete 85 157 142 126 110 126
12m 10kN Concrete 121 222 200 178 156 178
13m 12.1kN Concrete 74 137 123 109 96 109
13m 16.0kN Concrete 105 194 175 155 136 155
14m 11.0kN Concrete 63 117 105 93 82 93
14m 14.7kN Concrete 93 171 154 137 120 137
Number of bisector stays     2 3 3  
Number of inline stays   2       3

Table 18: MV Chicadee - unshielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 71 143 128 114 100 114
11m 13.3kN Concrete 105 210 189 168 147 168
12m 17.4kN Concrete 90 180 162 144 126 144
12m 10kN Concrete 127 254 228 203 178 203
13m 12.1kN Concrete 78 156 140 125 109 125
13m 16.0kN Concrete 111 221 199 177 155 177
14m 11.0kN Concrete 67 133 120 107 93 107
14m 14.7kN Concrete 98 196 176 157 137 157
Number of bisector stays     3 4 4  
Number of inline stays   2       4

Table 19: MV Chicadee - shielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 65 121 109 97 85 97
11m 13.3kN Concrete 96 178 160 142 125 142
12m 17.4kN Concrete 82 152 137 122 106 122
12m 10kN Concrete 116 215 193 172 150 172
13m 12.1kN Concrete 71 132 119 106 92 106
13m 16.0kN Concrete 102 188 169 150 131 150
14m 11.0kN Concrete 61 113 102 90 79 90
14m 14.7kN Concrete 90 166 149 133 116 133
Number of bisector stays     3 4 4  
Number of inline stays   2       4

Table 20: MV Bear - unshielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 57 115 103 92 80 92
11m 13.3kN Concrete 85 169 152 135 118 135
12m 17.4kN Concrete 72 145 130 116 101 116
12m 10kN Concrete 102 204 184 163 143 163
13m 12.1kN Concrete 63 125 113 100 88 100
13m 16.0kN Concrete 89 178 160 143 125 143
14m 11.0kN Concrete 54 107 97 86 75 86
14m 14.7kN Concrete 79 157 142 126 110 126
Number of bisector stays     3 4 4  
Number of inline stays   3       4

Table 21: MV Bear - shielded

  Intermediate: staggered vertical 600mm spacing Strain: in line, 0 degrees deviation Strain: 1-30 degrees deviation Strain: 31-60 degrees deviation Strain: 61-90 degrees deviation Strain: Terminal
Electrical clearance span (m) 225 200 200 200 200 200
Weight span (m) 1095          
Wind span (m) 11m 10.9kN Concrete 54 100 90 80 70 80
11m 13.3kN Concrete 79 148 133 118 103 118
12m 17.4kN Concrete 67 126 114 101 88 101
12m 10kN Concrete 95 178 160 143 125 143
13m 12.1kN Concrete 58 110 99 88 77 88
13m 16.0kN Concrete 83 156 140 124 109 124
14m 11.0kN Concrete 50 94 84 75 66 75
14m 14.7kN Concrete 73 137 124 110 96 110
Number of bisector stays     3 4 4  
Number of inline stays   3       4

Recommended planting depths for double-circuit lines

Pole Length (m) Planting depth (m)
11 1.8
12 2
13 2.2
14 2.3

 